Inspectors Perspective – February 2023

Core – Will no longer be notifying and scheduling with PV contractors when receiving a meter release from the AHJ they will be performing a “back feed” test and PV contractor will need to have all equipment in the on/closed position other than the AC disconnect which will need to remain off/open.

SouthWire – DJ Barajas presented on MC ap cable, the cable needs to be used with MCI fittings, the majority of MC fittings are approved, listed, and suitable for use with MC ap cable and meet 2020 NEC

Section 300.15. The wire type EGC, or bonding strip can also be terminated in a manner similar to standard MC. https://core.coop/my-cooperative/renewables/generation-interconnections/

Question – How do AHJ’s verify connectors are approved for use with the MC ap cable?

Consensus-AHJ’s will simply verify by inspecting the physical box the connectors are packaged and shipped in for all pertinent information to assure the cable is being terminated per its listing instructions, then simply spot check a few cable terminations. Reference 2020 NEC Sections 110.3(B) &300.15-“fittings and connectors shall be used only with the specific wiring methods for which they are designed and listed.”