A single 1500-W cord-and-plug-connected load on a 120-volt circuit would draw ___ amps. This requires a number ___ wire and a ___ circuit breaker for the branch circuit.

Select one:

  1. 12.5 – 14 AWG – 15-amp
  2. 8 – 14 AWG – 15-amp
  3. 10.5 – 14 AWG – 15-amp
  4. 12.5 – 12 AWG – 20-amp

Scroll down to see the answer.

The answer is d.12.5 – 12 AWG – 20-amp